Case Study: PRESTO W50 Process system
Heating up of an QVF 50 l reactor from -40 °C to +20 °C with a PRESTO W50 Process system
Objective
This case study tests the heating capacity of the JULABO PRESTO W50 Process system with a 50 l glass reactor. The PRESTO W50 is connected to the reactor via two 2 m metal hoses. The PRESTO W50 Process system has been programmed to heat up from -40 °C to +20 °C.
Test Conditions
Product | PRESTO W50 Process system | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity (Ethanol)
|
|||||||||||||||
Heating capacity | 6 kW | ||||||||||||||
Pump pressure | 0.5 bar | ||||||||||||||
Duration | 55 hr:min | ||||||||||||||
Test volume | 35 l | ||||||||||||||
Setpoint 1 | -40 °C | ||||||||||||||
Setpoint 2 | +20 °C | ||||||||||||||
Reactor | 50l QVF (glass) | ||||||||||||||
Tubing length | 2 m | ||||||||||||||
Fluid in unit | Thermal HL60 | ||||||||||||||
Fluid in reactor | Thermal HL60 |
Environment
Room temperature | 20 °C |
---|---|
Humidity | 45 % |
Voltage version | 400V/3PNPE/50Hz |
Control Parameters
XP | 0.2 K |
TN | 695 s |
TV | 85 s |
XPU | 15 K |