Case Study: PRESTO W50t Process system
Cooling a Büchiglas 50 l reactor from +150 °C to +20 °C with a PRESTO W50t Process system
Objective
This case study tests the cooling capacity of the JULABO PRESTO W50t Process system with a 50 l glass reactor. The PRESTO W50t is connected to the reactor via two 2 in. long metal hoses. The PRESTO W50t Process system has been programmed to cool down from +150 °C to +20 °C.
Test Conditions
Product | PRESTO W50t Process system | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity (Ethanol)
|
|||||||||||||||||
Heating capacity | 12 kW | ||||||||||||||||
Pump pressure | 7.3 psi | ||||||||||||||||
Duration | 1:09 hr:min | ||||||||||||||||
Test volume | 37.5 l | ||||||||||||||||
Setpoint 1 | +150 °C | ||||||||||||||||
Setpoint 2 | +20 °C | ||||||||||||||||
Reactor | 50l Büchiglas (glass) | ||||||||||||||||
Tubing length | 2 in. | ||||||||||||||||
Fluid in unit | Thermal HL60 | ||||||||||||||||
Fluid in reactor | Thermal H20S |
Environment
Room temperature | 20 °C |
---|---|
Humidity | 45 % |
Voltage version | 400V/3PNPE/50Hz |
Control Parameters
XP | 0.19 K |
TN | 695 s |
TV | 85 s |
XPU | 15 K |
Test Results
The PRESTO W50t Process system cools the reactor from +150 °C to +20 °C in 1:09 h.
Set point |
Temperature in the application |
Temperature in temperature control unit |