PRESTO W93x Process system
Full cooling capacity in the low temperature range
W93 process systems offer users high cooling capacity for dynamic applications even in the lowest temperature ranges. They work with natural refrigerants and are also very energy efficient thanks to state-of-the-art technologies.
The highly dynamic temperature control systems PRESTO are designed for high-precision temperature control for a wide range of applications such as reactor vessels or material stress tests. Moreover, by using efficient components, the process systems can compensate exothermic and endothermic reactions exceptionally fast. Permanent internal monitoring and self-lubricating pumps ensure a long life-time. In addition, numerous interfaces offer many remote control possibilities across networks or for integration into higher-level control systems.
Performance data depends on the mains voltage in the country of use. Please select:
Order number including voltage version | see refrigerant variants | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Working temperature range | -93 ... +250 °C | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Temperature stability | ±0.05 ... ±0.2 °C | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Cooling capacity
1 Performance specifications measured in accordance with DIN 12876. Cooling capacities up to 20 °C measured with ethanol; over 20 °C with thermal oil unless otherwise specified. Performance specifications apply at an ambient temperature of 20 °C. Performance values may differ with other bath fluids. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Dimensions
(W × L × H) |
36.6 x 54.3 x 75.6 in. |
Product Features
- External Pt100 sensor connection
- Alarm output
- Second external Pt100 sensor connection (accessory)
- Built-in 5.7’’ industrial color touchscreen
- Cooling capacity up to 21.5 kW
- Heating capacity up to 27 kW
- Analog connections, RS485, Profibus DP (accessory)
- Temperature stability ±0.05 ... ±0.2°C
- Integrated gas warning sensor, electrically wired and calibrated
- Intelligent warning and safety functions
- Ambient temperature range +5 °C to +40 °C
- Pump pressure up to 5.5 bar, max. flow rate 70 l/min
Technical data for PRESTO W93x
Dimensions (W × L × H) |
36.6 x 54.3 x 75.6 in. |
---|---|
Internal usable expansion volume | 36 l |
Minimal process volume | 30 l |
Active heat exchanger volume | 11 l |
Weight | 2292.8 lbs |
Pump connections | M38x1.5 male |
Cooling Water Connection | G¾ in. |
Working temperature range | -93 ... +250 °C |
---|---|
Temperature stability | ±0.05 ... ±0.2 °C |
Setting the resolution of the temperature display | 0.01 °C |
Temperature display resolution | 0.01 °C |
Ambient temperature | +5 ... +40 °C |
Performance data depends on the mains voltage in the country of use. Please select:
Cooling capacity
1 Performance specifications measured in accordance with DIN 12876. Cooling capacities up to 20 °C measured with ethanol; over 20 °C with thermal oil unless otherwise specified. Performance specifications apply at an ambient temperature of 20 °C. Performance values may differ with other bath fluids. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Power consumption | 75 A |
---|
Cooling of compressor | 2-stage Water |
---|---|
Cooling water pressure max. | 87 psi |
Max. heat dissipated by unit into cooling water | 53 kW |
to provide full cooling capacity according to catalog values | |
Cooling water temperature range | 10 ... 15 °C |
---|---|
Cooling water difference pressure | 29 ... 87 psi |
Cooling water consumption 2 | 32 l/min |
2 Cooling water consumption may vary outside recommended cooling water properties. |
Cooling water temperature range | 5 ... 30 °C |
---|---|
Cooling water difference pressure 3 | 7.3 ... 87 psi |
3 At cooling water temperatures of 25 °C and higher, the minimum differential pressure is 1 bar. |
Sound pressure level | 78 dbA |
---|---|
Classification according to DIN12876-1 |
Classification III (FL) |
IP Code according to IEC 60529 |
IP 20 |
Pump type | Gear Pump (Magnetically coupled) |
Interfaces | Alarm output / Ethernet / Modbus / Profibus optional / REG/EPROG optional / RS232 / RS485 optional / SD memory card / Standby-Input optional / USB |
---|---|
External pt100 sensor connection | integrated |
2nd external Pt100 sensor connection | accessory |
Integrated programmer | 8x60 steps |
Temperature control | ICC |
Absolute temperature calibration | 3 Point Calibration |
Temperature display | 5.7" TFT Touchscreen |
Temperature setting | Touchscreen |
9421933.N1.07 | 400V/3PNPE/50Hz (Without Plug, without cable) (R1270) |
---|---|
9421933.S1.07 | 400V/3PNPE/50Hz (Without Plug, without cable) (R449A) |
9421933.N1.17 | 460V/PPE/60Hz (Without Plug, without cable) (R1270) |
9421933.S1.17 | 460V/PPE/60Hz (Without Plug, without cable) (R449A) |
Accessory for PRESTO W93x
Downloads for PRESTO W93x
We would also be happy to send you our printed catalogs and brochures by post.
Request brochurePRESTO W93x Benefits
![Gaswarnsensor PRESTO](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_b941i2n0817tn48r7arts1p02d/-S65-FJPG/gaswarnsensor-presto.jpg)
Integrated gas detection sensor
For a high personal and process safety, the new W93 series is equipped with a gas detection sensor. The sensor is already electrically wired and calibrated upon delivery.
![Icon:Process systems Connections only on the front or rear side](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_nu285kush96fh639stqbode53v/-S65-FJPG/raumoptimierte-stellfl-c3-a4che.jpg)
Space-saving footprint
All connections as well supply and exhaust air are located at the front or rear, no venting grids on the sides, units can be placed close to each other or the application
![Icon Service Download instructions, case studies](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_j3c0alqbq574d65micm8ulna77/-S65-FJPG/downloads.jpg)
Services 24/7.
Around the clock availability. You can find suitable accessories, data sheets, manuals, case studies, and more at www.julabo.com.
![the JULABO Service network is available in many places around the world](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_nkhd1akgoh1nlfcsv70aee8h0j/-S65-FJPG/satisfied-customers.jpg)
Satisfied customers.
11 subsidiaries and more than 100 partners worldwide guarantee fast and qualified JULABO support.
Related Products
Products with similar properties
![Process system PRESTO W92 from JULABO view 1](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_291j4n0qst6ih7penue92m134j/-S96-FJPG/9421922-presto-w92-1.jpg)
![Process System PRESTO W92x from JULABO view 1](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_ib58oqvhrp51v51r8fnv1v5o6c/-S96-FJPG/9421923-presto-w92x-1.jpg)
![Process system PRESTO W91x from JULABO view 1](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_tmoei55b1h6ch26pfi8531m85t/-S96-FJPG/9421913.tt-presto-w91ttx-1.jpg)
![Process system PRESTO W93 from JULABO view 1](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_getvj8c0n14ap5gqmav21jvg2c/-S96-FJPG/16152442-presto-w93-1.jpg)
![Process system PRESTO W91 from JULABO view 1](https://dbyt75tph3sip.cloudfront.net/image/512030579289/image_i0i9hsnmn15ub8jgpjkp70vj32/-S96-FJPG/9421912-presto-w91-1.jpg)