Case Study: PRESTO W91tt Process system

Cooling a Büchiglas 100 l reactor from +20 °C to -50 °C with a PRESTO W91tt Process system

Objective

This case study tests the cooling capacity of the JULABO PRESTO W91tt Process system with a 100 l glass reactor. The PRESTO W91tt is connected to the reactor via two 2 m long metal hoses. The PRESTO W91tt Process system has been programmed to cool down from +20 °C to -50 °C.

Test Conditions

Product PRESTO W91tt Process system
Cooling capacity (Ethanol)
°C 20 0 -20 -40 -60 -80 -90
kW 11 11 11 10.5 8 2 0.8
Heating capacity 36 kW
Pump pressure 0.45 bar
Duration 2:30 hr:min
Test volume 100 l
Setpoint 1 +20 °C
Setpoint 2 -50 °C
Reactor 100l Büchiglas (glass)
Tubing length 2 m
Fluid in unit Thermal HL80
Fluid in reactor Thermal HL80

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 400V/3PNPE/50Hz

Test Results

The PRESTO W91tt Process system cools the reactor from +20 °C to -50 °C in 2:30 h.

Set point
Temperature in the application
Temperature in temperature control unit
Compare products